What is a DC pressure test?
DC Pressure Test: DC overvoltage test to ascertain suitability of plant for energisation. Equipment: Switchgear, transformers, cables, overhead lines, surge arresters, voltage transformers, current transformers, unit substations. Energisation: The application of Voltage to an item(s) of Equipment from the system.
Why Megger test is done only with DC voltage?
If we apply DC voltage then as we know Capacitor blocks the flow of DC, only leakage current due to imperfection of insulator will flow and hence the Resistance measured by Megger will actually represent Insulation Resistance. This is the reason, an Insulation Tester or Megger have DC voltage generator.
What is the difference between AC and DC high voltage testing?
Such a test applies a voltage to the DUT that is much higher than normal operating voltage; typically 1000V AC plus twice the normal operating voltage. A DC hipot test can usually be substituted for an AC hipot test. The best voltage for a DC hipot is normally higher than the AC test voltage by a factor of 1.414.
How does a DC hipot tester work?
DC voltage is applied to open (disconnected) windings by the Hipot tester or motor analyzer. The DC voltage potential in the windings is rapidly raised to a predetermined level, or raised in steps up to this level, depending on what test method is used.
What is the main purpose of a high voltage withstand test Hipot test?
Hipot test is the most common type of electrical safety test. Designed to verify that the insulation of a product is adequate enough to withstand high voltage. Performed by stressing the insulation of the product far beyond what it would encounter during normal use. Hence, the term “voltage withstand test”.
Why do we test high voltage?
High Voltage testing is usually performed to qualify the device to operate safely during rated electrical conditions, a way to check the effectiveness of its insulation. The objective sought during the high voltage testing will determine the type and amount of voltage applied and the acceptable current flow.
What is total DC current of megger?
Working Principle of Megger 500 Volt DC is sufficient for performing test on equipment range up to 440 Volts. 1000 V to 5000 V is used for testing for high voltage electrical systems. Deflecting coil or current coil connected in series and allows flowing the electric current taken by the circuit being tested.
Should the insulation have subjected to DC test?
DC test is preferred on equipment whose charging capacitance is very high, such as cables. DC voltage stress is considered much less damaging to insulation than AC voltages. Time of voltage application is not as critical with DC voltage as with AC voltage. Test can be stopped before equipment failure occurs.
Is insulation resistance test DC or AC?
Insulation resistance measurement, however, is non- destructive under normal test conditions. Carried out by applying a DC voltage with a smaller amplitude than for dielectric testing, it yields a result expressed in kΩ, MΩ, GΩ or TΩ. This resistance indicates the quality of the insulation between two conductors.
How much voltage applied for the Hipot test?
As per IEC 60950, The Basic test Voltage for Hipot test is the 2X (Operating Voltage) + 1000 V. The reason for using 1000 V as part of the basic formula is that the insulation in any product can be subjected to normal day-to-day transient over voltages.
Is DC hipot destructive?
One advantage of the DC Hipot test is the following: Although the test voltage can be high, the energy available to be discharged as an arc is small. Thus, arcs from a DC Hipot test are not destructive if the test is done properly.
How do you do a DC hipot?
Attach the high voltage lead to one of the isolated circuit phase conductors. Switch on the HIPOT Tester. Set the meter to 1000 Volts or pre decide DC Voltage. Push the “Test” button on the meter and after one minute observe the resistance reading.
Why do you need a DC test set?
DC tests are used mainly to do “ pressure tests ” on high voltage cables. Although the cables operate with AC, AC testing is not practical. The high capacitance of the cables necessitates AC test sets with a high kVA rating to be able to supply the capacitive current.
Why is insulation resistance test performed using DC voltage?
If the insulation resistance test is performed using an AC voltage, we end up measuring the impedance of the capacitive component and prevents us from obtaining the required insulation resistance. This is the reason why the insulation resistance test is performed using a DC voltage.
When to use DC or DC cable testing?
After engineering evaluation of the effectiveness of a test voltage and the risks to the cable system, high direct voltage may be considered appropriate for a particular application. If so, DC testing has the considerable advantage of being the simplest and most convenient to use.
How are DC and AC tests used in the lab?
DC tests are used mainly to do “pressure tests” on high voltage cables. Although the cables operate with AC, AC testing is not practical. The high capacitance of the cables necessitates AC test sets with a high kVA rating to be able to supply the capacitive current.